>Short circuit/interruption<trouble
ESSER FlexES: >Short circuit/interruption<
ESSER FlexES·0 views·0 field notes
What This Code Means
A condition indicating a short circuit or interruption on the connection line, which may cause the system to isolate segments of the loop using group separators.
Common Causes
- 1Interruptions or interchanged connections in the connection line
- 2Damaging the line due to insufficient bending radii
- 3Loop is too long or attenuation too high
Resolution Steps
Check for interruptions or interchanged connections in the connection line, damaging the line due to insufficient bending radii, or the loop being too long or attenuation too high. In the event of a short circuit within the loop, the cut-off relays of the corresponding group separators open and isolate the affected segment; isolated detectors are listed in the plain text display together with the fault parameter >Com. error<.
Manual References(1)
Related Codes
Related Questions
How do I reset a fault condition on the Esser FlexES panel after replacing a detector on the loop?How do I set up cause-and-effect programming on the FlexES panel to link detector zones to NAC outputs?What are the compatible battery specifications for the FlexES panel, and what is the procedure for battery replacement?