Addr Input Trouble On Monitor Moduletrouble
Fenwal FENWALNET 6000: Addr Input Trouble On Monitor Module
Fenwal FENWALNET 6000·0 views·0 field notes
What This Code Means
An open circuit has been detected in a monitor module's initiating device circuit (IDC).
Common Causes
- 1Discontinuity in the IDC wiring
- 2Missing 10k Ohm end-of-line resistor
- 3Loose connection at the module
Resolution Steps
Look for discontinuity in the initiating device circuit and check for a missing 10k end-of-line resistor.
Manual References(1)
Related Codes
Related Questions
What Fenwal-compatible detectors and modules can be used on the FENWALNET 6000 SLC loop?What do common FENWALNET 6000 trouble codes such as Ground Fault, Open Circuit, and Device Failure indicate?What are the pre-discharge and discharge sequences on the FenwalNET-6000 suppression system, and how does the abort function work?