Addr Input Trouble On Monitor Module
troubleFenwal FENWALNET 6000
55 views·0 field notes
What This Code Means
An open circuit has been detected in a monitor module's initiating device circuit (IDC).
Common Causes
- 1Discontinuity in the IDC wiring
- 2Missing 10k Ohm end-of-line resistor
- 3Loose connection at the module
Resolution Steps
Look for discontinuity in the initiating device circuit and check for a missing 10k end-of-line resistor.
Manual References(1)
Related Codes
Related Questions
How do I navigate the FENWALNET 6000 panel interface to view active alarms, troubles, and supervisory conditions?What are the pre-discharge and discharge sequences on the FenwalNET-6000 suppression system, and how does the abort function work?What is the SLC loop wiring configuration for the FENWALNET 6000, and does it support Class A and Class B?