FENWALNET 6000 Trouble Codes
20 trouble codes for the Fenwal FENWALNET 6000
24-Hour Trouble Reminder MessageAddr High Airflow On AnaLASER Interface ModuleAddr Input Trouble On Monitor ModuleAddr Line Volt Fault On Device TypeAddr Low Airflow On AnaLASER Interface ModuleAlarm Events Buffer Full MessageTypical Alarm Verification Message DisplayAR1 Short Circuit Trouble OnAR2 Open Circuit Trouble OnAR2 Short Circuit Trouble OnAR3 Open Circuit Trouble OnAR3 Short Circuit Trouble OnAR4 Open Circuit Trouble OnAR4 Short Circuit Trouble OnTypical Device Not Registered MessageLower Level Events Buffer Full MessageOutputs Silenced MessageTypical PAS Message DisplaySG1 Open Circuit Trouble OnSG1 Short Circuit Trouble On
A reminder that a trouble condition has been active and silenced for 24 hours without being resolved.
trouble
Excessively high air flow detected through the piping system of a high-sensitivity smoke detector (HSSD).
trouble
An open circuit has been detected in a monitor module's initiating device circuit (IDC).
trouble
A failure of the DC to DC converter in the device at the specified address, or insufficient voltage reaching the device.
trouble
Low air flow detected through the piping system of a high-sensitivity smoke detector (HSSD).
trouble
The internal buffer for alarm events has reached its maximum capacity.
maintenance
The panel is currently verifying a smoke detector signal to reduce nuisance alarms.
alarm
A short circuit has been detected in the field wiring connected to the main circuit board terminal TB12.
trouble
An open circuit has been detected in the field wiring connected to the main circuit board terminal TB11.
trouble
A short circuit has been detected in the field wiring connected to the main circuit board terminal TB11.
trouble
An open circuit has been detected in the field wiring connected to TB7, which is configured as a release circuit.
trouble
A short circuit has been detected in the field wiring connected to TB7, which is configured as a release circuit.
trouble
An open circuit has been detected in the field wiring connected to TB6, which is configured as a release circuit.
trouble
A short circuit has been detected in the field wiring connected to TB6, which is configured as a release circuit.
trouble
A device is present on the signaling line circuit but is not recognized in the system configuration.
trouble
The internal buffer for lower-level system events has reached its maximum capacity.
maintenance
The notification appliances or release outputs have been manually deactivated by an operator.
maintenance
The system is in Positive Alarm Sequence mode, providing a delay for investigation before full alarm activation.
alarm
An open circuit has been detected in the Notification Appliance Circuit 1 (NAC1) connected to TB5.
trouble
A short circuit has been detected in the Notification Appliance Circuit 1 (NAC1) connected to TB5.
trouble