FENWALNET 6000 Trouble Codes

20 trouble codes for the Fenwal FENWALNET 6000

24-Hour Trouble Reminder Message
A reminder that a trouble condition has been active and silenced for 24 hours without being resolved.
trouble
Addr High Airflow On AnaLASER Interface Module
Excessively high air flow detected through the piping system of a high-sensitivity smoke detector (HSSD).
trouble
Addr Input Trouble On Monitor Module
An open circuit has been detected in a monitor module's initiating device circuit (IDC).
trouble
Addr Line Volt Fault On Device Type
A failure of the DC to DC converter in the device at the specified address, or insufficient voltage reaching the device.
trouble
Addr Low Airflow On AnaLASER Interface Module
Low air flow detected through the piping system of a high-sensitivity smoke detector (HSSD).
trouble
Alarm Events Buffer Full Message
The internal buffer for alarm events has reached its maximum capacity.
maintenance
Typical Alarm Verification Message Display
The panel is currently verifying a smoke detector signal to reduce nuisance alarms.
alarm
AR1 Short Circuit Trouble On
A short circuit has been detected in the field wiring connected to the main circuit board terminal TB12.
trouble
AR2 Open Circuit Trouble On
An open circuit has been detected in the field wiring connected to the main circuit board terminal TB11.
trouble
AR2 Short Circuit Trouble On
A short circuit has been detected in the field wiring connected to the main circuit board terminal TB11.
trouble
AR3 Open Circuit Trouble On
An open circuit has been detected in the field wiring connected to TB7, which is configured as a release circuit.
trouble
AR3 Short Circuit Trouble On
A short circuit has been detected in the field wiring connected to TB7, which is configured as a release circuit.
trouble
AR4 Open Circuit Trouble On
An open circuit has been detected in the field wiring connected to TB6, which is configured as a release circuit.
trouble
AR4 Short Circuit Trouble On
A short circuit has been detected in the field wiring connected to TB6, which is configured as a release circuit.
trouble
Typical Device Not Registered Message
A device is present on the signaling line circuit but is not recognized in the system configuration.
trouble
Lower Level Events Buffer Full Message
The internal buffer for lower-level system events has reached its maximum capacity.
maintenance
Outputs Silenced Message
The notification appliances or release outputs have been manually deactivated by an operator.
maintenance
Typical PAS Message Display
The system is in Positive Alarm Sequence mode, providing a delay for investigation before full alarm activation.
alarm
SG1 Open Circuit Trouble On
An open circuit has been detected in the Notification Appliance Circuit 1 (NAC1) connected to TB5.
trouble
SG1 Short Circuit Trouble On
A short circuit has been detected in the Notification Appliance Circuit 1 (NAC1) connected to TB5.
trouble