AR1 Short Circuit Trouble Ontrouble
Fenwal FENWALNET 6000: AR1 Short Circuit Trouble On
Fenwal FENWALNET 6000·1 view·0 field notes
What This Code Means
A short circuit has been detected in the field wiring connected to the main circuit board terminal TB12.
Common Causes
- 1Damaged wiring insulation
- 2Incorrect termination at TB12
- 3Moisture in the conduit
Resolution Steps
Troubleshoot Release-1 wiring by breaking-up the circuit to isolate the short circuit to a specific leg.
Manual References(1)
Related Codes
Related Questions
What Fenwal-compatible detectors and modules can be used on the FENWALNET 6000 SLC loop?What do common FENWALNET 6000 trouble codes such as Ground Fault, Open Circuit, and Device Failure indicate?What are the pre-discharge and discharge sequences on the FenwalNET-6000 suppression system, and how does the abort function work?