AR2 Open Circuit Trouble On
troubleFenwal FENWALNET 6000
56 views·0 field notes
What This Code Means
An open circuit has been detected in the field wiring connected to the main circuit board terminal TB11.
Common Causes
- 1Broken field wire
- 2Loose connection at terminal block
- 3Missing end-of-line device
Resolution Steps
Look for discontinuity in Release-2 field wiring. Refer to Paragraph 2-11 of the manual.
Manual References(1)
Related Codes
Related Questions
How do I navigate the FENWALNET 6000 panel interface to view active alarms, troubles, and supervisory conditions?What are the pre-discharge and discharge sequences on the FenwalNET-6000 suppression system, and how does the abort function work?What is the SLC loop wiring configuration for the FENWALNET 6000, and does it support Class A and Class B?