Addr Line Volt Fault On Device Typetrouble
Fenwal FENWALNET 6000: Addr Line Volt Fault On Device Type
Fenwal FENWALNET 6000·1 view·0 field notes
What This Code Means
A failure of the DC to DC converter in the device at the specified address, or insufficient voltage reaching the device.
Common Causes
- 1SLC wiring resistance or capacitance limits exceeded
- 2Low line voltage (below 17V)
- 3Internal device hardware failure
Resolution Steps
Check SLC wiring resistance and capacitance. Verify device LED is flashing. Use Handheld Programmer to test the device. Ensure line-voltage is at least 17V. Replace device if it fails tests.
Manual References(1)
Related Codes
Related Questions
What Fenwal-compatible detectors and modules can be used on the FENWALNET 6000 SLC loop?What do common FENWALNET 6000 trouble codes such as Ground Fault, Open Circuit, and Device Failure indicate?What are the pre-discharge and discharge sequences on the FenwalNET-6000 suppression system, and how does the abort function work?