Addr Line Volt Fault On Device Type
troubleFenwal FENWALNET 6000
56 views·0 field notes
What This Code Means
A failure of the DC to DC converter in the device at the specified address, or insufficient voltage reaching the device.
Common Causes
- 1SLC wiring resistance or capacitance limits exceeded
- 2Low line voltage (below 17V)
- 3Internal device hardware failure
Resolution Steps
Check SLC wiring resistance and capacitance. Verify device LED is flashing. Use Handheld Programmer to test the device. Ensure line-voltage is at least 17V. Replace device if it fails tests.
Manual References(1)
Related Codes
Related Questions
How do I navigate the FENWALNET 6000 panel interface to view active alarms, troubles, and supervisory conditions?What are the pre-discharge and discharge sequences on the FenwalNET-6000 suppression system, and how does the abort function work?What is the SLC loop wiring configuration for the FENWALNET 6000, and does it support Class A and Class B?