GROUND FAULTtrouble
Fire-Lite MS-9600: GROUND FAULT
Fire-Lite MS-9600·0 views·0 field notes
What This Code Means
This condition indicates a ground fault, specifically zero impedance between the Fire Alarm Control Panel (FACP) and ground.
Common Causes
- 1Zero impedance between FACP and ground
- 2Conduit alone used for earth ground without a solid building earth connection
- 3Improper wire type, gauge, or run length for system circuits
Resolution Steps
Attach solid earth ground wire to grounding stud. Connect ground wire from Earth Ground terminal to a solid building earth, as conduit alone will not provide a reliable earth ground. Disconnect all sources of power before servicing and verify that wire sizes are adequate for all initiating and indicating device loops.