What This Code Means
Excessively high air flow detected through the piping system of a high-sensitivity smoke detector (HSSD).
Common Causes
- 1Leaks in the HSSD piping system
- 2Airflow needs re-normalization
- 3Broken sampling pipe
Resolution Steps
Look for leaks in the HSSD's piping. Use LaserNET to troubleshoot. Re-normalize airflow if necessary according to the AnaLASER II manual.
Manual References(1)
Related Codes
Related Questions
What Fenwal-compatible detectors and modules can be used on the FENWALNET 6000 SLC loop?What do common FENWALNET 6000 trouble codes such as Ground Fault, Open Circuit, and Device Failure indicate?What are the pre-discharge and discharge sequences on the FenwalNET-6000 suppression system, and how does the abort function work?