Addr High Airflow On AnaLASER Interface Module
troubleFenwal FENWALNET 6000
51 views·0 field notes
What This Code Means
Excessively high air flow detected through the piping system of a high-sensitivity smoke detector (HSSD).
Common Causes
- 1Leaks in the HSSD piping system
- 2Airflow needs re-normalization
- 3Broken sampling pipe
Resolution Steps
Look for leaks in the HSSD's piping. Use LaserNET to troubleshoot. Re-normalize airflow if necessary according to the AnaLASER II manual.
Manual References(1)
Related Codes
Related Questions
How do I navigate the FENWALNET 6000 panel interface to view active alarms, troubles, and supervisory conditions?What are the pre-discharge and discharge sequences on the FenwalNET-6000 suppression system, and how does the abort function work?What is the SLC loop wiring configuration for the FENWALNET 6000, and does it support Class A and Class B?