AR2 Short Circuit Trouble On
troubleFenwal FENWALNET 6000
52 views·0 field notes
What This Code Means
A short circuit has been detected in the field wiring connected to the main circuit board terminal TB11.
Common Causes
- 1Pinched wires in the enclosure
- 2Shorted release device
- 3Wiring fault
Resolution Steps
Troubleshoot Release-2 wiring by breaking-up the circuit to isolate the short circuit to a specific leg.
Manual References(1)
Related Codes
Related Questions
How do I navigate the FENWALNET 6000 panel interface to view active alarms, troubles, and supervisory conditions?What are the pre-discharge and discharge sequences on the FenwalNET-6000 suppression system, and how does the abort function work?What is the SLC loop wiring configuration for the FENWALNET 6000, and does it support Class A and Class B?