AR2 Short Circuit Trouble Ontrouble
Fenwal FENWALNET 6000: AR2 Short Circuit Trouble On
Fenwal FENWALNET 6000·1 view·0 field notes
What This Code Means
A short circuit has been detected in the field wiring connected to the main circuit board terminal TB11.
Common Causes
- 1Pinched wires in the enclosure
- 2Shorted release device
- 3Wiring fault
Resolution Steps
Troubleshoot Release-2 wiring by breaking-up the circuit to isolate the short circuit to a specific leg.
Manual References(1)
Related Codes
Related Questions
What Fenwal-compatible detectors and modules can be used on the FENWALNET 6000 SLC loop?What are the pre-discharge and discharge sequences on the FenwalNET-6000 suppression system, and how does the abort function work?What do common FENWALNET 6000 trouble codes such as Ground Fault, Open Circuit, and Device Failure indicate?