AR3 Open Circuit Trouble On
troubleFenwal FENWALNET 6000
44 views·0 field notes
What This Code Means
An open circuit has been detected in the field wiring connected to TB7, which is configured as a release circuit.
Common Causes
- 1Discontinuity in Combo-1 field wiring
- 2Disconnected solenoid
- 3Broken wire
Resolution Steps
Look for discontinuity in Combo-1 field wiring. Refer to Paragraph 2-10.2.
Manual References(1)
Related Codes
Related Questions
How do I navigate the FENWALNET 6000 panel interface to view active alarms, troubles, and supervisory conditions?What are the pre-discharge and discharge sequences on the FenwalNET-6000 suppression system, and how does the abort function work?What is the SLC loop wiring configuration for the FENWALNET 6000, and does it support Class A and Class B?