AR3 Open Circuit Trouble Ontrouble
Fenwal FENWALNET 6000: AR3 Open Circuit Trouble On
Fenwal FENWALNET 6000·0 views·0 field notes
What This Code Means
An open circuit has been detected in the field wiring connected to TB7, which is configured as a release circuit.
Common Causes
- 1Discontinuity in Combo-1 field wiring
- 2Disconnected solenoid
- 3Broken wire
Resolution Steps
Look for discontinuity in Combo-1 field wiring. Refer to Paragraph 2-10.2.
Manual References(1)
Related Codes
Related Questions
What Fenwal-compatible detectors and modules can be used on the FENWALNET 6000 SLC loop?What do common FENWALNET 6000 trouble codes such as Ground Fault, Open Circuit, and Device Failure indicate?What are the pre-discharge and discharge sequences on the FenwalNET-6000 suppression system, and how does the abort function work?