Typical Device Not Registered Messagetrouble
Fenwal FENWALNET 6000: Typical Device Not Registered Message
Fenwal FENWALNET 6000·1 view·0 field notes
What This Code Means
A device is present on the signaling line circuit but is not recognized in the system configuration.
Common Causes
- 1New device added without running Auto-Learn
- 2Incorrect device address
- 3Device replaced with a different model type
Resolution Steps
Perform the Auto-Learn routine or update the site-specific programming via the FCS Configuration Program.
Manual References(1)
Related Codes
Related Questions
What Fenwal-compatible detectors and modules can be used on the FENWALNET 6000 SLC loop?What do common FENWALNET 6000 trouble codes such as Ground Fault, Open Circuit, and Device Failure indicate?What are the pre-discharge and discharge sequences on the FenwalNET-6000 suppression system, and how does the abort function work?