AC Loss (shown only when requested)trouble

Fire-Lite MS-5024: AC Loss (shown only when requested)

Fire-Lite MS-5024·2 views·0 field notes

What This Code Means

The AC ON indicator turns off and the trouble LED turns on when the AC line voltage drops below the Low Line threshold.

Common Causes

  • 1AC line voltage drops below the Low Line threshold (102VAC for MS-5024)
  • 2AC Brownout condition
  • 3Complete loss of primary AC power

Resolution Steps

Enter Troubleshoot Mode by pressing MODE 8768 and [ENTER/STORE]. Press A followed by the [ENTER/STORE] key to display the AC input voltage. Verify that the AC line voltage is within the normal range (115VAC for MS-5024). Restore AC power to the panel; the control panel will turn on the AC LED and clear the trouble message upon restoral.

Manual References(3)

Field Notes

Loading field notes...
Sign in to share a field note

Related Codes

Related Questions