MS-5024 Trouble Codes
22 trouble codes for the Fire-Lite MS-5024
AC LossAC Loss (shown only when requested)Annunciator FaultPrimary C. Number Communication FaultSecondary C. Communications FaultDrillGround faultFailed Up/DownloadGround faultLow batteryBell 1 circuit faultBell 2 circuit faultNo batterySupervisory Alarm Zone # nSUPX (X=Zone Number)System Off NormalPrimary Phone Line FaultSecondary Phone Line FaultZone 1 disabledAlarm Zone # nZone n disabledTrouble on zone n
The panel has lost AC power or the voltage has dropped below the brownout threshold.
trouble
The AC ON indicator turns off and the trouble LED turns on when the AC line voltage drops below the Low Line threshold.
trouble
Communication has been lost between the main control panel and a remote annunciator.
trouble
The Digital Alarm Communicator Transmitter (DACT) failed to communicate with the primary central station.
trouble
The Digital Alarm Communicator Transmitter (DACT) failed to communicate with the secondary central station.
trouble
The fire drill function has been manually activated to test notification appliances.
maintenance
The control panel has detected that a supervised circuit, such as a zone or NAC, is in contact with earth ground.
trouble
The panel failed to complete a remote programming upload or download session.
trouble
The control panel has detected a ground fault condition on the supervised field wiring or initiating device circuits.
trouble
The standby battery voltage is below the critical threshold required for proper operation.
trouble
A fault condition (open or short) exists on Notification Appliance Circuit 1.
trouble
A fault condition (open or short) exists on Notification Appliance Circuit 2.
trouble
The panel does not detect any battery connected to the charging terminals.
trouble
A supervisory condition has been detected on the specified zone, indicating a fire protection system component is off-normal.
supervisory
A condition indicating that a waterflow sensing device, its wiring, or a tamper switch is in an off-normal state.
supervisory
The system is in a non-standard operating mode, such as Troubleshoot or Programming mode.
maintenance
The panel has detected a loss of voltage or connection on the primary telephone line.
trouble
The panel has detected a loss of voltage or connection on the secondary telephone line.
trouble
A specific initiating zone has been manually deactivated by a user, preventing it from triggering alarms or reporting troubles.
trouble
An initiating device on the specified zone has entered the alarm state.
alarm
The specified initiating zone has been manually disabled and will not report alarms.
maintenance
An open circuit or wiring fault has been detected on the specified initiating zone.
trouble