Bell 2 circuit faulttrouble
Fire-Lite MS-5024: Bell 2 circuit fault
Fire-Lite MS-5024·1 view·0 field notes
What This Code Means
A fault condition (open or short) exists on Notification Appliance Circuit 2.
Common Causes
- 1Broken field wiring
- 2Short circuit in notification devices
- 3Missing EOL resistor
Resolution Steps
Check NAC 2 wiring for opens or shorts. Verify the presence of the correct EOL resistor. Use Troubleshoot Mode to check circuit voltage.