SUPX (X=Zone Number)supervisory
Fire-Lite MS-5024: SUPX (X=Zone Number)
Fire-Lite MS-5024·0 views·0 field notes
What This Code Means
A condition indicating that a waterflow sensing device, its wiring, or a tamper switch is in an off-normal state.
Common Causes
- 1Wiring to the waterflow valve or tamper switch has been cut
- 2Tamper switch has been activated
- 3Waterflow sensing device activation
Resolution Steps
When the supervisory condition has been cleared (condition is restored and the reset switch has been pressed) the control panel will turn off the supervisory LED, deactivate the supervisory relay(s), clear the display of the SUP message, and shut off the piezo sounder. Note: For any zone programmed for Supervisory auto resettable, the Reset key does not need to be pressed to clear the zone.