001 Ground
troubleKidde Aegis 2.0
70 views·0 field notes
What This Code Means
The control unit has detected an unintended connection to earth ground on the field wiring.
Common Causes
- 1Connections to earth ground on field wiring
- 2Improper earth-ground offset voltage (nominal is 6.60 Vdc)
- 3Leakage currents from high-power circuits like motors, fans, or air-conditioning into the ground return
- 4Grounding both ends of a drain wire or shield providing a current path
Resolution Steps
Check for connections to earth ground on field wiring whose removal restores proper earth-ground offset voltage of 6.60 Vdc nominal.
Manual References(2)
Related Codes
Related Questions
How do I program the Kidde Aegis 2.0 cross-zone detection so that two circuits must activate before the releasing circuit fires?What is the correct procedure to test the manual release function on the Aegis 2.0 without discharging the agent?What is the difference between Abort Mode 1 (UL 864) and Abort Mode 3 (IRI) on the Aegis 2.0?