001 Groundtrouble
Kidde Aegis 2.0: 001 Ground
Kidde Aegis 2.0·0 views·0 field notes
What This Code Means
The control unit has detected an unintended connection to earth ground on the field wiring.
Common Causes
- 1Connections to earth ground on field wiring
- 2Improper earth-ground offset voltage (nominal is 6.60 Vdc)
- 3Leakage currents from high-power circuits like motors, fans, or air-conditioning into the ground return
- 4Grounding both ends of a drain wire or shield providing a current path
Resolution Steps
Check for connections to earth ground on field wiring whose removal restores proper earth-ground offset voltage of 6.60 Vdc nominal.