Aegis 2.0 Trouble Codes

40 trouble codes for the Kidde Aegis 2.0

trb
Microprocessor or PCB failure
trouble
001 Ground
The control unit has detected an unintended connection to earth ground on the field wiring.
trouble
002
AC Voltage is below 85% of nominal
trouble
003
Primary Power Supply Unit (PSU) Output Voltage fault
trouble
004
No secondary power (battery) connected or detected
trouble
005
Battery charger fault
trouble
Low Battery
This condition indicates that the battery voltage has fallen below the required threshold for reliable standby operation.
trouble
007
Reversed battery polarity
trouble
008
Detector Circuit #1 open circuit
trouble
009
Detector Circuit #2 open circuit
trouble
010
Detector Circuit #3 or Waterflow circuit open circuit
trouble
011
Manual Release circuit open circuit
trouble
012
Supervisory Circuit #1 open circuit
trouble
013
Supervisory Circuit #2 open circuit
trouble
014
Invalid Abort activation
trouble
015
Abort circuit open circuit
trouble
016
Agent Release Circuit (ARC) 1 short circuit
trouble
017
Agent Release Circuit (ARC) 2 short circuit
trouble
018
Notification Appliance Circuit (NAC) 1 short circuit
trouble
019
Notification Appliance Circuit (NAC) 2 short circuit
trouble
020
Notification Appliance Circuit (NAC) 3 short circuit
trouble
021
Agent Release Circuit (ARC) 1 open circuit
trouble
022
Agent Release Circuit (ARC) 2 open circuit
trouble
023
Notification Appliance Circuit (NAC) 1 open circuit
trouble
024
Notification Appliance Circuit (NAC) 2 open circuit
trouble
025
Notification Appliance Circuit (NAC) 3 open circuit
trouble
026
ARC 1 Not Open Circuit (Unexpected load detected)
trouble
027
ARC 2 Not Open Circuit (Unexpected load detected)
trouble
028
NAC 1 Not Open Circuit (Unexpected load detected)
trouble
029
NAC 2 Not Open Circuit (Unexpected load detected)
trouble
030
NAC 3 Not Open Circuit (Unexpected load detected)
trouble
031
RS232 Serial Cable Connected
trouble
035
ARC #1 Outputs Disabled (Pseudo-Trouble)
maintenance
036
ARC #2 Outputs Disabled (Pseudo-Trouble)
maintenance
037
NAC #1 Outputs Disabled (Pseudo-Trouble)
maintenance
038
NAC #2 Outputs Disabled (Pseudo-Trouble)
maintenance
039
NAC #3 Output Disabled (Pseudo-Trouble)
maintenance
Battery Disconnect
Automatic battery disconnection due to critical low voltage
trouble
System Supervisory
The control unit has detected a change in state of one or both of its supervisory input circuits, or its PCB mounted Output Disable switch.
supervisory
Supervisory Signal
Change in state of a supervisory input circuit or Output Disable switch
supervisory