INSPIRE N16 Trouble Codes
20 trouble codes for the Notifier INSPIRE N16
AC Failure (LSB is PMB address 1-5)AIO Addr 1-10 Duplicate AddressAIO Address 1-10 Comm LossASPIRATIONBattery Low (LSB is PMB address 1-5)Cellular Card No ConnectivityCharger Fail (LSB is PMB address 1-5)Default database. Please program.EPROM ERRORGROUND FAULTHISTORY 80%LOOP CONTINUITY TEST FAIL LOOP 1-10MAPPING IN PROGRESS LOOP 1-9NVRAM BATTPANEL DOOR SUPERVISORYPOTS Line 1 FailurePRIMARY AMP 1-4 OVERCURRENTSELF TEST FAILEDTRANSMIT/ RECEIVE ERROR ABOVE LIMIT ON LOOP 1-10UNPROGRAMMED DEVICE ON LOOP 1-10
Loss of primary AC power to the power supply module.
trouble
Two or more devices on the AIO bus share the same address.
trouble
Communication failure between the main panel and an AIO peripheral device.
trouble
A supervisory condition reported by an intelligent aspiration (air sampling) detector.
supervisory
The backup battery voltage has dropped below the required threshold.
trouble
The cellular card is present but cannot connect to the cellular network.
trouble
The power supply's battery charging circuit is not functioning correctly.
trouble
The panel is running on a factory default database and has not been configured.
trouble
A hardware memory failure detected during the panel's self-diagnostic routine.
trouble
An unintentional connection between the system wiring and earth ground.
trouble
The system event history log is reaching its maximum capacity.
maintenance
The panel detected a break in the SLC loop wiring during a continuity test.
trouble
The panel is currently performing a topology map of the SLC loop.
maintenance
The internal battery that maintains the panel's non-volatile memory is low.
trouble
The panel enclosure door is open or the tamper switch is activated.
supervisory
The panel has lost the dial tone or connection on the primary telephone line.
trouble
The primary amplifier has detected an overcurrent condition on its output.
trouble
An automated diagnostic test on a detector or module has failed.
trouble
Excessive data errors detected on the SLC loop, indicating poor signal quality.
trouble
A device is physically present on the SLC loop but has not been added to the panel's database.
trouble