What This Code Means

A trouble condition or fault exists on phone line 1.

Common Causes

  • 1Phone line voltage drops below 3 VDC
  • 2Telephone service is interrupted for longer than 45 seconds
  • 3Physical fault in the phone line

Resolution Steps

Monitor the DC voltage present on the lines to ensure it does not drop below 3 VDC for longer than 40 seconds. Verify that the telephone service has not been interrupted. Ensure the phone lines are programmed properly according to the manual's programming steps.