P4: SK-5207 Trouble Code | Fire Alarm Resource Center
P4
trouble
Silent Knight SK-5207
83 views·0 field notes
What This Code Means
The panel has detected a short between any power source and earth ground.
Common Causes
1Short between terminals 12, 15, 18, 24, 26, 28, 30, 32, or 34 and earth ground
2Short between the batteries and earth ground
3Faulty field wiring
Resolution Steps
To determine the location of the short, place a DC volt meter with ground on terminal 1 and positive on terminal 52. The meter should be continuously fluctuating between 0 and 2.5 volts. Remove and leave off field wiring from the panel until the meter reads in this range. You can also use Accu-Zone Troubleshooting (Mode 25) to determine the location.