GROUND FAULT: 4010ES Trouble Code | Fire Alarm Resource Center
GROUND FAULT
trouble
Simplex 4010ES
67 views·0 field notes
What This Code Means
An electrical circuit is shorted to ground, which can impair system communication or power.
Common Causes
1Electrical circuit shorted to earth ground
2Fiber optic transmitter/receiver module touching the supporting bracket
3Missing 10 K resistor (R62) on fiber optic network card (565-818)
4Remote PC's 3-prong plug grounding the service port cable
5Field wiring defects or failed isolation circuits
Resolution Steps
Run the Earth Fault search diagnostic from the front panel. If the results do not isolate the source, disable each NAC one at a time, disconnect the AUX power, and disconnect the N2 communications from the panel, checking each time to see if the fault clears. For fiber optic modules, use a strip of insulating material to isolate the bracket from the module.