29 trouble codes for the Edwards EST iO64

Loop 1 uncfgrd alarm
A device on loop 1 that is not programmed went into alarm.
alarm
Loop 1 uncfgrd trouble
A device on loop 1 that is not programmed went into trouble.
trouble
Loop 1 map mismatch
The loop 1 map in RAM and the loop 1 map in the database do not match.
trouble
Loop 1 over limits
There are too many devices on loop 1.
trouble
Loop 1 device 000
A device on loop 1 has an address set to zero.
trouble
Loop 2 fault
A short or open was detected on loop 2 affecting the communications between the panel and the devices on the loop.
trouble
Loop 2 map fault
A mapping fault was detected on loop 2 while the panel was mapping the devices.
trouble
Loop 2 card fault
The loop 2 card is not present or it is not working.
trouble
Ground fault
The panel detected a ground fault.
trouble
Battery charger
The panel detected a battery charger trouble condition; the charger may not be able to charge the batteries.
trouble
Battery low
The batteries are low on power.
trouble
Battery missing
The battery is no longer connected.
trouble
AC power
There is a problem with the panel’s AC power.
trouble
Aux power 1
The control panel detected a trouble condition on the continuous AUX power circuit 1.
trouble
Aux power 2
The control panel detected a trouble condition on the resettable AUX power circuit 2.
trouble
Self test fault
A fault was detected while testing the panel’s internal subsystems (memory, flash, code).
trouble
Internal fault
The control panel detected an internal hardware or software error.
trouble
Dialer line 1 fault
A ground fault or line fault was detected on line 1 of the dialer.
trouble
Dialer delivery fail
The dialer failed to deliver a message to the receiver.
trouble
Dialer configuration
The dialer is not programmed or has unverified configuration.
trouble
Net Comm Fault 01
Communications between the panel and network receiver 01 failed.
trouble
IPGateway Trouble
IP Gateway configuration is invalid.
trouble
Fw Download Failed
Firmware update failed to store the Image.bin into panel flash memory.
trouble
NAC 1 trouble
An open or short was detected on NAC 1 or there is a problem with the EOL.
trouble
Printer trouble
The printer is either offline, out of paper, or disconnected.
trouble
Annunciator 1 trouble
An open or short was detected on annunciator 1.
trouble
Waterflow active
A waterflow condition has been detected, indicating water movement in the sprinkler system.
alarm
Supervisory active
A supervisory condition has been detected by the system.
supervisory
Zone maintenance alert
A maintenance alert was detected for a zone.