iO64 Trouble Codes
29 trouble codes for the Edwards EST iO64
Loop 1 uncfgrd alarmLoop 1 uncfgrd troubleLoop 1 map mismatchLoop 1 over limitsLoop 1 device 000Loop 2 faultLoop 2 map faultLoop 2 card faultGround faultBattery chargerBattery lowBattery missingAC powerAux power 1Aux power 2Self test faultInternal faultDialer line 1 faultDialer delivery failDialer configurationNet Comm Fault 01IPGateway TroubleFw Download FailedNAC 1 troublePrinter troubleAnnunciator 1 troubleWaterflow activeSupervisory activeZone maintenance alert
A device on loop 1 that is not programmed went into alarm.
alarm
A device on loop 1 that is not programmed went into trouble.
trouble
The loop 1 map in RAM and the loop 1 map in the database do not match.
trouble
There are too many devices on loop 1.
trouble
A device on loop 1 has an address set to zero.
trouble
A short or open was detected on loop 2 affecting the communications between the panel and the devices on the loop.
trouble
A mapping fault was detected on loop 2 while the panel was mapping the devices.
trouble
The loop 2 card is not present or it is not working.
trouble
The panel detected a ground fault.
trouble
The panel detected a battery charger trouble condition; the charger may not be able to charge the batteries.
trouble
The batteries are low on power.
trouble
The battery is no longer connected.
trouble
There is a problem with the panel’s AC power.
trouble
The control panel detected a trouble condition on the continuous AUX power circuit 1.
trouble
The control panel detected a trouble condition on the resettable AUX power circuit 2.
trouble
A fault was detected while testing the panel’s internal subsystems (memory, flash, code).
trouble
The control panel detected an internal hardware or software error.
trouble
A ground fault or line fault was detected on line 1 of the dialer.
trouble
The dialer failed to deliver a message to the receiver.
trouble
The dialer is not programmed or has unverified configuration.
trouble
Communications between the panel and network receiver 01 failed.
trouble
IP Gateway configuration is invalid.
trouble
Firmware update failed to store the Image.bin into panel flash memory.
trouble
An open or short was detected on NAC 1 or there is a problem with the EOL.
trouble
The printer is either offline, out of paper, or disconnected.
trouble
An open or short was detected on annunciator 1.
trouble
A waterflow condition has been detected, indicating water movement in the sprinkler system.
alarm
A supervisory condition has been detected by the system.
supervisory
A maintenance alert was detected for a zone.
maintenance