005
troubleKidde Aegis 2.0
51 views·0 field notes
What This Code Means
Battery charger fault
Common Causes
- 1PCB charging circuit failure
- 2Power supply output voltage error
- 3Defective battery
Resolution Steps
Measure Power Supply voltage (27.6 Vdc) at PSU J2. If correct, replace PCB. If not correct, replace power supply.
Manual References(2)
Related Codes
Related Questions
How do I program the Kidde Aegis 2.0 cross-zone detection so that two circuits must activate before the releasing circuit fires?What is the correct procedure to test the manual release function on the Aegis 2.0 without discharging the agent?What is the difference between Abort Mode 1 (UL 864) and Abort Mode 3 (IRI) on the Aegis 2.0?