Low Battery
troubleKidde Aegis 2.0
57 views·0 field notes
What This Code Means
This condition indicates that the battery voltage has fallen below the required threshold for reliable standby operation.
Common Causes
- 1Battery voltage is less than 25.0 Vdc in the absence of primary power
- 2Battery voltage falls below 19.5 V
- 3Batteries have been in service for 36 months or more
- 4Primary AC power loss causing battery discharge
Resolution Steps
Check battery voltage, must be greater than 25.0 Vdc in the absence of primary power. The battery will be automatically disconnected when the battery voltage falls below 17 volts.
Manual References(2)
Related Codes
Related Questions
How do I program the Kidde Aegis 2.0 cross-zone detection so that two circuits must activate before the releasing circuit fires?What is the correct procedure to test the manual release function on the Aegis 2.0 without discharging the agent?What is the difference between Abort Mode 1 (UL 864) and Abort Mode 3 (IRI) on the Aegis 2.0?