010trouble
Kidde Aegis 2.0: 010
Kidde Aegis 2.0·0 views·0 field notes
What This Code Means
Detector Circuit #3 or Waterflow circuit open circuit
Common Causes
- 1Broken field wiring
- 2Missing 5.1K Ohm EOL resistor
- 3Incorrect resistor value
Resolution Steps
Look for discontinuity in Detector #3/Waterflow wiring. Check for missing or incorrect value 5.1K resistor.