012
troubleKidde Aegis 2.0
45 views·0 field notes
What This Code Means
Supervisory Circuit #1 open circuit
Common Causes
- 1Broken field wiring
- 2Missing 5.1K Ohm EOL resistor
- 3Incorrect resistor value
Resolution Steps
Look for discontinuity in Supervisory #1 wiring. Check for missing or incorrect value 5.1K resistor.
Manual References(2)
Related Codes
Related Questions
How do I program the Kidde Aegis 2.0 cross-zone detection so that two circuits must activate before the releasing circuit fires?What is the correct procedure to test the manual release function on the Aegis 2.0 without discharging the agent?What is the difference between Abort Mode 1 (UL 864) and Abort Mode 3 (IRI) on the Aegis 2.0?