4100ES Trouble Codes
47 trouble codes for the Simplex 4100ES
AC FailALARM SILENCEDCDAMPERCEXHAUSChannel FailClass A TroubleCOFIRECOPRI2COSUPVCPRESSDAMPERDISABLEDEarth Fault SearchExtra DeviceFIREGround FaultGVMONIDNet Power Monitor TroubleInstall ModeLATSUPVNo Answer/Bad AnswerNO OUTNOT TSTOutput AbnormalDIAGNOSTIC LED ACTIVEBMUX OVERRIDE POLL FAILED TRANSPONDERSCO 6 MONTH ALMOST EXPIRED LOG ENABLECO 12 MONTH ALMOST EXPIRED LOG ENABLELOG CLEARED TROUBLES GLOBAL ACKSUPERVISORY VERIFICATION GROUP 0 ACTIVESUPERVISORY VERIFICATION GROUP 1 ACTIVESUPERVISORY VERIFICATION GROUP 2 ACTIVESUPERVISORY VERIFICATION GROUP 3 ACTIVESUPERVISORY VERIFICATION GROUP 4 ACTIVESUPERVISORY VERIFICATION GROUP 5 ACTIVESUPERVISORY VERIFICATION GROUP 6 ACTIVESUPERVISORY VERIFICATION GROUP 7 ACTIVERECURRING TROUBLE FILTER ACTIVATEDRWATERShort CircuitTDAMPERUNSUPPWALKTESTWATERWATERFLOW MONITOR ZONE ALARMWSCWSO
AC power is not present or is too low for proper system operation.
trouble
This condition indicates that the building's notification appliances have been manually silenced while an alarm or warning condition is still active on the panel.
alarm
A supervisory condition specifically for a controlled damper.
supervisory
An exhaust system supervisory condition has been detected.
supervisory
A complete communication failure has occurred on a specific system channel or loop.
trouble
A break in the wiring has occurred on a Class A (Style 6 or 7) circuit.
trouble
A Carbon Monoxide Fire Alarm condition has been detected.
alarm
A Carbon Monoxide Priority 2 event has been detected.
alarm
A Carbon Monoxide supervisory condition is active.
supervisory
A pressure-related supervisory condition is active.
supervisory
A fire or smoke damper is not in its normal operating position.
supervisory
A point has been manually suppressed and will not report alarm conditions or other status changes; the system indicates a trouble condition for each disabled point.
trouble
The panel is actively performing a search to locate and isolate a ground fault.
trouble
A device is responding at an address that has not been programmed into the system configuration.
trouble
A standard fire alarm condition has been triggered.
alarm
A circuit has developed an electrical path to the earth ground.
trouble
Gate Valve Monitor supervisory condition.
supervisory
The IDNet card has detected an issue with its internal or loop power monitoring.
trouble
The system is in Install Mode, which groups troubles for uninstalled devices into a single condition.
maintenance
A latching supervisory condition has been detected that requires a manual reset.
supervisory
A programmed device is either not responding or is sending invalid data to the panel.
trouble
During a TrueAlert ES self-test, no light or sound output was detected from the appliance.
trouble
The TrueAlert ES appliance did not return a test result before the self-test cycle ended.
trouble
An output circuit, such as a NAC, is not in its expected electrical state.
trouble
The system diagnostic LED is currently active, indicating a diagnostic process is running or a hardware fault is being signaled.
trouble
The system failed to poll transponders during a BMUX override condition.
trouble
The Carbon Monoxide (CO) sensor is approximately 6 months away from its expiration date.
trouble
The Carbon Monoxide (CO) sensor is approximately 12 months away from its expiration date.
trouble
Indicates that cleared troubles have been globally acknowledged in the system log.
trouble
Supervisory verification group 0 is currently active and processing a point state change.
supervisory
Supervisory verification group 1 is currently active and processing a point state change.
supervisory
Supervisory verification group 2 is currently active and processing a point state change.
supervisory
Supervisory verification group 3 is currently active and processing a point state change.
supervisory
Supervisory verification group 4 is currently active and processing a point state change.
supervisory
Supervisory verification group 5 is currently active and processing a point state change.
supervisory
Supervisory verification group 6 is currently active and processing a point state change.
supervisory
Supervisory verification group 7 is currently active and processing a point state change.
supervisory
The system has activated a filter to suppress recurring intermittent trouble signals to prevent nuisance notifications.
trouble
A water-related supervisory condition has been detected.
supervisory
This message appears when a short circuit is detected on the IDNet or IDNAC channel.
trouble
A trouble or supervisory condition related to a damper has been detected.
supervisory
The installed appliance is not compatible with the TrueAlert ES Self-Test feature.
trouble
The system is currently in a test mode that allows for automatic resetting of alarms.
maintenance
Waterflow has been detected in the sprinkler system.
supervisory
This condition indicates that a waterflow device connected to a monitor zone has been activated, typically by water moving through the sprinkler system.
alarm
Waterflow Supervisory Closed condition.
supervisory
Waterflow Supervisory Open condition.
supervisory